Central wastewater heat recovery for hotels and commercial kitchens
Kitchen wastewater drains at up to around 45 °C. The heat exchangers usually use it without filters, upstream of the grease separator.

Hotels, restaurants and commercial kitchens, for example in hospitals, barracks, care homes and canteens, are especially suited to AWT-928 units.

The wastewater reaches the heat exchangers directly at up to around 45 °C and preheats the fresh water to around 20 to 30 °C.
- No separation, usually no filter: installation upstream of the grease separator is possible, which keeps the system economical.
- Even with toilet wastewater: if the wastewater cannot be separated for structural reasons, heat recovery remains effective.
Worked example
A 4-star hotel with 100 beds and 60% occupancy has around 21,900 overnight stays a year. With a typical water consumption of around 260 litres per overnight stay, that is around 16 m³ a day, of which around 6 m³ is hot water. The collected wastewater also contains toilet flushing water, so it arrives at only around 25 °C. This preheats the cold water from 10 to around 17 to 19 °C. The result is around 20,000 kWh a year, roughly 7,500 to 36,000 kWh depending on the operation.
A commercial kitchen serving 1,000 meals a day reaches around 25,000 kWh a year if it cooks on 250 days (staff canteen), and around 35,000 kWh if it operates on all 365 days (hospital, care home).
What this heat is worth today
Worked example: hotel with 100 beds: 20,000 kWh saved per year, valued at current energy prices (indicative figure, not a commitment):
| Energy source replaced | Net price, as of November 2026 | Value per year |
|---|---|---|
| Natural gas | 10 ct/kWh | around €2,200 |
| Heating oil | 1.50 €/L | around €3,800 |
| Electricity (direct electric heating) | 23 ct/kWh | around €4,600 |
As of November 2026, rounded, excluding VAT. Calculated with typical boiler efficiencies: natural gas 90 %, heating oil 80 % (so 1 litre of heating oil supplies around 8 kWh of useful heat), electricity 100 %. Prices: household end-customer prices on energie.gv.at (Austria; heating oil of 26/10/2026, natural gas and electricity of 01/08/2026). Your prices may differ, and we are happy to calculate with your figures.
The figures come from individual installations and apply to their operating conditions. They are not a commitment for your installation. Only the quotation and order confirmation are binding.
Matching product
Wastewater heat exchangers, FB and AWT series
Wastewater heat recovery with unpressurised film flow: for wastewater with lint, fibres and particles, from 1 to 30 L/s of wastewater.