Skip to content
FERCHER GmbHwww.fercher.at/en/products/wastewater-heat-exchangers/
Heat exchangers from Austria, quality since 1988+43 676 606 95 40office@fercher.at
Request a calculationCall
Menu
EN

Wastewater heat exchangers, FB and AWT series

Wastewater heat recovery with unpressurised film flow: for wastewater with lint, fibres and particles, from 1 to 30 L/s of wastewater.

Request a calculation

At FERCHER, wastewater does not run through closed channels. It flows as a free, unpressurised film over the heat exchanger plates, so fibres, lint and particles simply pass through. A profile on the plates creates turbulence that increases heat transfer and carries dirt along.

In normal operation the heat recovery system needs very little maintenance. For normal treated sewage a pre-filter is usually not needed. For inspection, take off the covers while the system keeps running.

Properties

  • Unpressurised film flow on the wastewater side, very little maintenance in normal operation
  • Cleaning without interrupting operation
  • Few wearing parts, no electrical components
  • Cross-counterflow and induced turbulence on the wastewater and service water sides
  • Entirely stainless steel, material no. 1.4404, other materials available
  • Can be combined with a wastewater heat pump, including for low temperatures
  • Also suitable for wastewater cooling alone

Customer information on CE marking and the EU Pressure Equipment Directive (PDF)

From production

Absorber plates of a large FB heat exchanger in production

Functions

Panels can be removed without operation interruption
Panels can be removed without operation interruption
Calming and distribution of the wastewater flow
Calming and distribution of the wastewater flow
Wastewater distribution onto heat exchanger plates
Wastewater distribution onto heat exchanger plates
Pressureless wastewater film flow for optimal heat transfer
Pressureless wastewater film flow for optimal heat transfer
Robust: few wearing parts, no electrical components
Robust: few wearing parts, no electrical components

Type overview

TypeMax. wastewater flowMax. service water flowMax. service water pressure (PN)Empty weightSpray cleaning systemCleanable without interruption
AWT-924-K1.0 L/s1.0 L/s6.0 bar32 kgoptionalYes
AWT-924-S1.0 L/s1.0 L/s6.0 bar38 kgYesYes
AWT-9282.0 L/s1.4 L/s6.0 bar132 kgYesYes
FB-12.0 L/s1.4 L/s6.0 bar117 kgoptionalYes
FB-2/S-1-14.0 L/s2.8 L/s6.0 bar206 kgoptionalYes
FB-2/S-2-22.0 L/s1.0 L/s6.0 bar206 kgoptionalYes
FB-4/S-1-18.0 L/s5.6 L/s6.0 bar428 kgoptionalYes
FB-4/S-2-24.0 L/s2.0 L/s6.0 bar429 kgoptionalYes
FB-6/S-1-112.0 L/s8.4 L/s6.0 bar552 kgoptionalYes
FB-6/W-2-26.0 L/s3.0 L/s6.0 bar658 kgoptionalYes
FB-8/S-1-116.0 L/s11.2 L/s6.0 bar687 kgoptionalYes
FB-8/W-2-18.0 L/s11.2 L/s6.0 bar951 kgoptionalYes
FB-8/W-2-28.0 L/s4.0 L/s6.0 bar897 kgoptionalYes
FB-12/W-2-212.0 L/s6.0 L/s6.0 bar1,137 kgoptionalYes
FB-12/W-2-112.0 L/s16.8 L/s6.0 bar1,205 kgoptionalYes
FB-16/W-2-116.0 L/s22.4 L/s6.0 bar1,459 kgoptionalYes
FB-16/W-2-216.0 L/s8.0 L/s6.0 bar1,376 kgoptionalYes
FB-30/W-2-130.0 L/s42.0 L/s6.0 bar1,775 kgoptionalYes
FB-30/W-2-230.0 L/s15.0 L/s6.0 bar2,096 kgoptionalYes

All types in detail

AWT-924-K

AWT-924-KAWT-924-K – 2
Max. wastewater flow
1.0 L/s
Max. service water flow
1.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
32 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

AWT-924-S

AWT-924-SAWT-924-S – 2
Max. wastewater flow
1.0 L/s
Max. service water flow
1.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
38 kg
Spray cleaning system
Yes
Cleanable without interruption
Yes

AWT-928

AWT-928AWT-928 – 2
Max. wastewater flow
2.0 L/s
Max. service water flow
1.4 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
132 kg
Spray cleaning system
Yes
Cleanable without interruption
Yes

FB-1

Max. wastewater flow
2.0 L/s
Max. service water flow
1.4 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
117 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-2/S-1-1

Max. wastewater flow
4.0 L/s
Max. service water flow
2.8 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
206 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-2/S-2-2

Max. wastewater flow
2.0 L/s
Max. service water flow
1.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
206 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-4/S-1-1

FB-4/S-1-1FB-4/S-1-1 – 2
Max. wastewater flow
8.0 L/s
Max. service water flow
5.6 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
428 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-4/S-2-2

Max. wastewater flow
4.0 L/s
Max. service water flow
2.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
429 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-6/S-1-1

FB-6/S-1-1FB-6/S-1-1 – 2
Max. wastewater flow
12.0 L/s
Max. service water flow
8.4 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
552 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-6/W-2-2

Max. wastewater flow
6.0 L/s
Max. service water flow
3.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
658 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-8/S-1-1

FB-8/S-1-1FB-8/S-1-1 – 2
Max. wastewater flow
16.0 L/s
Max. service water flow
11.2 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
687 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-8/W-2-1

FB-8/W-2-1FB-8/W-2-1 – 2
Max. wastewater flow
8.0 L/s
Max. service water flow
11.2 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
951 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-8/W-2-2

FB-8/W-2-2FB-8/W-2-2 – 2
Max. wastewater flow
8.0 L/s
Max. service water flow
4.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
897 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-12/W-2-2

FB-12/W-2-2FB-12/W-2-2 – 2
Max. wastewater flow
12.0 L/s
Max. service water flow
6.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
1,137 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-12/W-2-1

FB-12/W-2-1FB-12/W-2-1 – 2
Max. wastewater flow
12.0 L/s
Max. service water flow
16.8 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
1,205 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-16/W-2-1

FB-16/W-2-1FB-16/W-2-1 – 2
Max. wastewater flow
16.0 L/s
Max. service water flow
22.4 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
1,459 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-16/W-2-2

FB-16/W-2-2FB-16/W-2-2 – 2
Max. wastewater flow
16.0 L/s
Max. service water flow
8.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
1,376 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-30/W-2-1

Max. wastewater flow
30.0 L/s
Max. service water flow
42.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
1,775 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

FB-30/W-2-2

Max. wastewater flow
30.0 L/s
Max. service water flow
15.0 L/s
Max. service water pressure (PN)
6.0 bar
Empty weight
2,096 kg
Spray cleaning system
optional
Cleanable without interruption
Yes

Used in these industries

Frequently asked questions

Does a wastewater heat exchanger need a pre-filter?

As a rule, no. FERCHER wastewater heat exchangers also work with high dirt loads, for example lint, fibres or plastic particles.

Can the heat exchanger be cleaned during operation?

Yes. The wastewater flows openly without pressure, and the covers can be removed without interrupting operation. In normal operation cleaning is rarely needed. The unit must still be inspected: for the first time within four weeks of commissioning and at least once a year after that.

Can the wastewater heat exchanger be combined with a heat pump?

Yes. This makes it possible to use low-temperature wastewater as well, such as sewer water at around 8 °C or treated water.

Can it be installed outdoors?

Yes. The service water circuit then needs a frost-proof medium.

Which safety device does the service water circuit need?

The operator limits the pressure on the service water side to the permissible operating pressure stated in the data sheet, usually 6 bar, with a pressure reducer or safety valve, including against pressure surges from the supply network.

Do your wastewater heat exchangers carry a CE mark?

No, and that is what the law requires. According to our classification, the FB and AWT wastewater heat exchangers for water and water-glycol up to 6 bar are below the limits of EU Pressure Equipment Directive 2014/68/EU. For such equipment, Article 4(3) requires design and manufacture in accordance with sound engineering practice, and instructions for use. They must not carry the CE mark of this Directive. In Austria this is governed by § 7 of the Duale Druckgeräteverordnung.

Where are the heat exchangers made?

Design and manufacture take place entirely in Austria.

FERCHER GmbH · St. Thomas 10 · 9400 Wolfsberg · Austria · +43 676 606 95 40 · office@fercher.at · www.fercher.at