FW-100

- Max. exhaust gas flow
- 1,500 m³/h
- Nominal output N1*
- 8 kW
- Nominal output N2*
- 12 kW
- Empty weight
- 43 kg
- Extractable unit
- optional
- Condensate drain
- optional
Flat-tube economizers for heavily contaminated exhaust gas: wide gaps instead of fine fins, cleanable without removal, 11 types from 1,500 to 52,000 m³/h.
Fine fins clog quickly in exhaust gas. FERCHER exhaust gas heat exchangers therefore use flat tubes with a gap of around 9 mm on the gas side. This keeps the pressure drop low and gives dirt room to pass.
Cleaning without removal: shut off the exhaust gas, let the unit cool down, take off the covers and clean with a brush, compressed air or a high-pressure cleaner.
Customer information on CE marking and the EU Pressure Equipment Directive (PDF)
For heavily contaminated exhaust gas: the module is pulled out without removing the heat exchanger, cleaned for example in an immersion bath, and pushed back in. The extraction bracket is not included and is offered separately.
ABK-H-A extraction console: fully welded console in stainless steel 1.4571 for H-A types, around 35 kg. Data sheet (PDF)
The FW series comes in several sizes. On X2 to X4 types, two to four modules work together. This raises the gas flow to as much as 52,000 m³/h.






| Type | Max. exhaust gas flow | Nominal output N1* | Nominal output N2* | Empty weight | Extractable unit | Condensate drain |
|---|---|---|---|---|---|---|
| FW-100 | 1,500 m³/h | 8 kW | 12 kW | 43 kg | optional | optional |
| FW-200 | 2,500 m³/h | 25 kW | 68 kW | 146 kg | optional | optional |
| FW-300 | 3,500 m³/h | 37 kW | 99 kW | 185 kg | optional | optional |
| FW-400 | 5,000 m³/h | 52 kW | 139 kW | 231 kg | optional | optional |
| FW-400-H-A | 5,000 m³/h | 52 kW | 139 kW | 316 kg | Yes | Yes |
| FW-600 | 7,000 m³/h | 76 kW | 203 kW | 302 kg | optional | optional |
| FW-600-H-A | 7,000 m³/h | 76 kW | 203 kW | 392 kg | Yes | Yes |
| FW-1000 | 13,000 m³/h | 138 kW | 367 kW | 486 kg | optional | optional |
| FW-1000-X2 | 26,000 m³/h | 277 kW | 735 kW | 930 kg | optional | optional |
| FW-1000-X3 | 39,000 m³/h | 415 kW | 1,102 kW | 1,338 kg | optional | optional |
| FW-1000-X4 | 52,000 m³/h | 553 kW | 1,470 kW | 1,742 kg | optional | optional |
* Definition of nominal power N1: Flue gas from natural gas burner (air ratio 1.2) at 250 °C, flue gas volumeflow selected such as to create a pressure loss of 200 Pa, heating water from 60 °C to 80 °C
* Definition of nominal power N2: Flue gas from natural gas burner (air ratio 1.2) at 400 °C, flue gas volumeflow selected such as to create a pressure loss of 500 Pa, heating water from 60 °C to 80 °C













3D CAD data (STEP) is provided for installation planning. The data sheet and order confirmation take precedence.
Instead of fine fins we use flat tubes with gaps of around 9 mm. Dirt passes through the wide spaces and the pressure loss stays low.
Up to 500 °C in the standard material. With special stainless steel, for example material number 1.4841, up to 800 °C is possible.
Remove the covers and clean with a brush, compressed air or a high-pressure cleaner, with no need to remove the unit. On H-A types the modules can be pulled out, for example for an immersion bath.
Usually not. The heat exchangers are designed to run directly on contaminated exhaust gas and are also suitable upstream of filters for gas cooling.
No, and that is what the law requires. According to our classification, the FW exhaust gas heat exchangers for water and water-glycol up to 10 bar and 110 °C are below the limits of EU Pressure Equipment Directive 2014/68/EU. For such equipment, Article 4(3) requires design and manufacture in accordance with sound engineering practice, and instructions for use. They must not carry the CE mark of this Directive. In Austria this is governed by § 7 of the Duale Druckgeräteverordnung.
Under EU Pressure Equipment Directive 2014/68/EU. Water is a Group 2 fluid there. For such liquids a category only starts above 10 bar and above 10,000 bar·L. Our largest type, the FW-1000-X4, reaches 2,540 bar·L at 10 bar. You will find more in our customer information under Downloads.
Design and manufacture take place entirely in Austria.
The installation must automatically route the exhaust gas past the heat exchanger through a bypass or shut off the gas source if the heating water pump fails, the flow falls below the minimum, power or control fails, or the water exceeds its permissible temperature. If auxiliary energy such as power or compressed air fails, the bypass must open. Safety valves are required directly upstream and downstream of the heat exchanger, together with a temperature limiter that cuts off the exhaust gas supply at the latest at the permissible water temperature. The operator provides these safety devices.