Using flue gas heat in a heating plant
Case study of a district heating supplier: an FW-600 in the existing flue gas duct saves an extrapolated 252,000 kWh per year.

A district heating supplier had an FW-600 retrofitted into the existing flue gas duct, between the flue gas fan and the chimney. The flue gas cools from around 190 °C to around 110 °C and heats the heating water from around 52 °C to around 65 °C.
| Key figure | Value |
|---|---|
| Flue gas | approx. 190 °C → approx. 110 °C |
| Heating water | approx. 52 °C → approx. 65 °C |
| Continuous output per system diagram | approx. 51 kW |
| Spot measurement | 38 kW momentary output, 187.7 → 109 °C |
| Saved in 2 months of operation | approx. 42,000 kWh |
| Saved per year, extrapolated | approx. 252,000 kWh |
| Investment incl. duct conversion at the time | approx. €16,000 |
| Payback at the time | 0.9 to 1.3 years at 5 to 7 ct/kWh |
The installed unit is an earlier design. You will find the current types under exhaust gas heat exchangers.
What this heat is worth today
252,000 kWh saved per year, valued at current energy prices (indicative figure, not a commitment):
| Energy source replaced | Net price, as of November 2026 | Value per year |
|---|---|---|
| Natural gas | 10 ct/kWh | around €28,000 |
| Heating oil | 1.50 €/L | around €47,300 |
| Electricity (direct electric heating) | 23 ct/kWh | around €58,000 |
As of November 2026, rounded, excluding VAT. Calculated with typical boiler efficiencies: natural gas 90 %, heating oil 80 % (so 1 litre of heating oil supplies around 8 kWh of useful heat), electricity 100 %. Prices: household end-customer prices on energie.gv.at (Austria; heating oil of 26/10/2026, natural gas and electricity of 01/08/2026). Your prices may differ, and we are happy to calculate with your figures.
The figures come from individual installations and apply to their operating conditions. They are not a commitment for your installation. Only the quotation and order confirmation are binding.
Matching product
Exhaust gas and flue gas heat exchangers, FW series
Flat-tube economizers for heavily contaminated exhaust gas: wide gaps instead of fine fins, cleanable without removal, 11 types from 1,500 to 52,000 m³/h.
Learn more