Wastewater heat recovery in swimming pools and spas
Shower wastewater leaves the building at around 31 °C. This heat can be used to preheat cold water.

Example: thermal spa in Germany
Around 1,000 visitors a day and around 20 m³ of hot water a day for the showers. The wastewater leaves the showers at an average of 31 °C and runs through three AWT-924 units in the basement. They preheat the cold water from 8 °C to 20 °C. By calculation that is around 279 kWh a day and around 101,900 kWh a year with daily operation.

Example: peat bath in Austria
In a spa facility, two AWT-928 units work in series, here mounted one above the other. They also use the peat bath wastewater. The built-in spray system maintains efficiency. Other arrangements are possible.
Example: thermal spa with two AWT-928 units
Two AWT-928 units hang in series from the basement ceiling and use around 18 m³/h of wastewater at around 35 °C. They preheat around 7.2 m³/h of fresh water from around 8 °C to 20 °C, recovering around 100 kW.
What this heat is worth today
Thermal spa in Germany: 101,900 kWh saved per year, valued at current energy prices (indicative figure, not a commitment):
| Energy source replaced | Net price, as of November 2026 | Value per year |
|---|---|---|
| Natural gas | 10 ct/kWh | around €11,300 |
| Heating oil | 1.50 €/L | around €19,100 |
| Electricity (direct electric heating) | 23 ct/kWh | around €23,400 |
As of November 2026, rounded, excluding VAT. Calculated with typical boiler efficiencies: natural gas 90 %, heating oil 80 % (so 1 litre of heating oil supplies around 8 kWh of useful heat), electricity 100 %. Prices: household end-customer prices on energie.gv.at (Austria; heating oil of 26/10/2026, natural gas and electricity of 01/08/2026). Your prices may differ, and we are happy to calculate with your figures.
The figures come from individual installations and apply to their operating conditions. They are not a commitment for your installation. Only the quotation and order confirmation are binding.